Service & Support. Answers for industry. Operating system update with ProSave. FAQ • July 2008. V2.1, Entry ID: 19701610. This entry is from the Service&Support portal of Siemens AG, Sector. System of the operator panel does not match the software version used. Hardware and software described. Since deviations cannot be pre-cluded entirely, we cannot guarantee full agreement. However, the data in this manual are reviewed regularly and any necessary cor-rections included in subsequent editions. Suggestions for improve-ment are welcomed. Technical data subject to change. Siemens AG 1996.

To upload / download the HMI program from panel, you need a software named PROSAVE from Siemens. Prosave come with many version, and not all of them could upload/download your OP7 or OP3 program. To create new program on OP7 or 3, you can use Protool software. PROSAVE is also included on siemens Protool software. If you cannot find the prosave, you may search the free download on google. Cause the software is free and downloadable But please noted that not all OP7 and OP3 are able to be upload/download.

Though you could upload, you may cannot edit it with protool. All you can do is only transfer the uploaded program to the IDENTICAL operator Panel. You may also need the special cable (usually rs 232). You can searching for another information from HTTP://support.automation.siemens.com. You have clicked on the '?' Button for search help.

To search the site, enter your search terms in the box labeled 'search the site' and hit Enter. Some tips for better search results. Precede each search term with a '+', as follows:. +Modbus +TCP Otherwise, any post with either term will match. Use double quotes around phrases, as follows:. +'Allen Bradley' +ethernetOtherwise, posts containing these words in separate locations will match.

To exclude a word, precede it with a '-', as follows:. +Modbus -Plus This will return only posts containing 'Modbus' but NOT containing 'Plus'. Note that common words (and, that, etc.) and words shorter than 2 characters are automatically excluded from searches. Select the categories for which you would like to see messages displayed. Applications Application Questions and Problems Automation Business The Business of Automation and Control Communications Communications systems and equipment.

Siemens

Siemens Prosave Software Download

Engineering Engineering and workplace issues. HMI Human-Machine Interface and SCADA. Information Information resources, documentation. Languages Programming languages. Motion Control Motion control, servos, steppers, etc. Networking Local and wide area networking in factory automation. Open Control Open interfaces, software and hardware PCs in Automation Computers in manufacturing; also hardware discussion.

Siemens Prosave Software Download

PLCs PLCs and related questions. Power Generation Power generation equipment control. Process Control Continuous process industries, DCS questions. Sensors Sensor technologies. Software in Automation Software, including programming, OS issues, etc.

To establish an open communication between your laptop/desktop and an HMI both devices must be set up on the same subnet. If they are not set up on the same subnet you will not be able to talk to the device. Example: Laptop =I.P 192.168.0.15 subnet 255.255.255.0 HMI= I.P 192.168.0.50 subnet 255.255.255.0 Step 1: Go to the windows home page of the HMI device. Upon entering the home screen a secondary will appear noting the following: Transfer, Start, Control Panel, & Taskbar. Step 2: Click on Control Panel, select “Profinet”.

A secondary will appear with a check box indicating “Profinet I/O enabled”. Check this box.

The section below the check box indicates the device name given to the HMI. Exit the Profinet window, go back to the icon selection screen. Step 3: Scroll down in the icon list to find “Transfer Settings “and open it. Be sure that on Channel 2 Ethernet is selected and the “Enable Channel” selection box is checked. There is a button to right named “Advanced” click it. Step 4: From the advanced button you should be directed to a Network Configuration window.

In the center is list of network drivers installed on the device. Select the appropriate driver and click the “Properties” button located on the bottom right of the screen. This will take you to the Onboard LAN Ethernet screen. Here you have the option to have the HMI obtain the IP automatically or you can specify the desired I.P address. Click Specify I.P address and enter the I.P & subnet desired. Be sure that it matches the subnet on your Laptop. Note: You cannot use the same I.P address of your laptop/desktop as the one entered on the HMI.

The last digit must be different. Step 5: Plug in a cat5 RJ45 Ethernet cable to the HMI and connect it to your Laptop/Desktop.

Step 6: Exit out and go back to the windows home screen of the HMI to see Transfer, Start, Control Panel, & Taskbar. Hit the transfer button. The HMI will state “connecting to device”. This is fine, the HMI must be in transfer mode for the laptop to extract the program. Step 7: Load Prosave. The first screen to populate upon launch will be the General Tab. Here you will select the HMI device and the method of communication which here is Ethernet.

Once you select Ethernet it will prompt you to enter the I.P address of the HMI you just configured or noted. Enter the I.P address of the HMI in this selection. Next, select the Backup Tab on the top and select what data type you would like to extract from the HMI. Last select the directory or location you would like to save the backup file. Once completed click the “Start Backup” button and the program will commence back up.